7.7 Replacing Engine Control Module

1. Set RAS to STOP.

2. Turn OFF the 200A DC circuit breaker (PN-6x-T) or disconnect the output connector

(CE-3x2).

3. Disconnect wire harnesses on ECM top to bottom.

4. Release the ECM captive latch and slide the ECM out of its housing.

5. Check new ECM DIP switch configuration per Table 4.4 (page 61).

6. Verify 120V/240V jumpers in the 120V position.

7. Install new ECM card. Verify card edges are in rails and latch card in place.

8. Verify RAS is OFF.

9. Reconnect wire harnesses top to bottom.

10. Set RAS to AUTO.

11. Verify APU runs for the one minute self-test.

12. Check and clear any alarms.

Release ECM captive latch

and slide ECM from its

housing. Perform steps in

reverse order to replace

ECM.

Fig. 7-7, ECM (Alpha P/N 744-726-23)