Alpha Technologies AlphaGen PN-6x-T 7.5kW 48Vdc User Manual

Page 61

Advertising
background image

042-288-B0-001, Rev. A2

61

4.0

The Engine Control Module, continued
4.5

Alarm Classifications, continued

Minor Alarms:
Minor alarms indicate a system fault which, though not indicative of imminent system failure

or shutdown, requires service attention before the condition worsens. A site check by service

personnel is recommended.
• Control Fail (Latching – after five activations): A control failure between the ECM and

the generator set. Typically this means the engine did not start or stop when commanded

to do so. The alarm is cleared when the Reset command is issued or the manual stop

switch is activated.

• Alternator Off (Non-latching): This alarm is active if the generator controller has

disabled the alternator output. A generator controller may disable the alternator output if

the output voltage cannot be held above some threshold.

• Self-test Fail (Latching): Activates when the most recent generator self-test fails. The

alarm is cleared when the Reset command is issued, the manual stop switch is activated

or another Self-Test command is issued.

• Low Ignition Battery: The generator’s ignition battery voltage has fallen below 11.5Vdc.

Alarm is cleared when battery voltage rises above 12Vdc indicating battery recovery has

begun. The low ignition battery voltage does not trigger an alarm during engine cranking.

Auto Mode Disabled: The position of the ECM control select switch. When the Run-

Auto-Stop (RAS) switch is in a manual (STOP or RUN) position, the ECM has no control

over engine operation and therefore raises an alarm. This is a hardware ‘lockout’ input

and cannot be changed via status monitoring.

• Tamper: One of the enclosure doors is open. The alarm clears when the door is closed

(disabled).

• DC Bus Fault: The power system DC bus voltage, as measured at the ECM, is less

than the DC bus voltage (programmable - default = 49V). This alarm clears automatically

when the bus voltage exceeds 2V above nominal (i.e., 50Vdc in a 48V system). Note the

alarm clears, but the generator starts when DC bus level drops to 49Vdc or lower.

• Engine Disabled: Command to disable normal operation of the generator set. When set

to DISABLE the engine is shutdown under all conditions. A Minor Alarm indicator is active

if this switch is set to DISABLE. The engine is disabled by software after five consecutive

Low Fuel alarms, or five consecutive Control Fail alarms. This alarm is cleared by issuing

a “Reset” command or when the “Manual Stop” switch is activated.

• Output Circuit Breaker OFF or Disabled (PN-6x-T Only): No ECM indication. Verify

circuit breaker position visually.

Notifications:
Notifications represent important information not urgent enough to be considered an alarm.

There are currently two notifications.
• Line Failure: The ECM’s determination of the state of AC line voltage. Loss of AC utility

input is one of the criteria for starting the generator.

• Service Required: Routine maintenance of the engine/generator is due. This alarm

activates when the Service Countdown reaches 0. It is cleared by depressing the service

timer reset button for five seconds (Refer to Section 7.0, System Maintenance, for further

information).

Advertising
This manual is related to the following products: