11 maintenance functions – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48Vdc User Manual

Page 68

Advertising
background image

68

042-288-B0-001, Rev. A2

4.0

The Engine Control Module, continued
4.10 ECM Self-test, continued

The following programmable, internal ECM variables control automatic self-tests.
• Autotest Interval: The number of days between automatic tests.
Autotest Countdown:
• Autotest Duration: Each Autotest is measured in minutes. The test duration is 10

minutes.

Manually Enabling the Autotest Feature:
Use SW5-8 to enable the Autotest feature with a 14-day test interval. The first autotest begins

14 days from the time the ECM is powered up with the configuration switch changed from 0 to

1 (OFF to ON). To disable the autotest sequence, put SW5-8 in the OFF position and restart

the ECM. On power up, the ECM looks for a change

in the switch position before it changes

the test control parameters.

1. Go to the site on the day of the week and time of day you want the self-test to occur.

2. Disconnect and remove the ECM.

3. Turn OFF SW5-8.

4. Install and re-power the ECM briefly (15 second minimum powerup time). If AC is

present, this can be done by connecting J6 (AC line, the 2-position mate-n-lock plug at

the bottom of the ECM). Disconnect and remove the ECM (again).

5. Turn ON SW5-8.

6. Reinstall the ECM with all connectors.

The self-test will occur 14 days from the time the ECM is powered.

4.11 Maintenance Functions

The ECM monitors time between periodic maintenance of the engine-generator. The service

interval is the number of hours of engine runtime between servicing. When the engine

runtime is equal to service interval, the ECM activates the Service Required notification and

turns on the amber notification LED. The default value of Service Interval is 100 hours, and

can be programmed from 0 to 250.
Service Due is the number of engine runtime hours before the next periodic maintenance is

required. Pressing and holding the Service Reset switch for five seconds resets the service

counter and it is updated with the current value of the service interval.

Advertising
This manual is related to the following products: