042-288-B0-001, Rev. A2

51

3.0

Installation, continued

3.14 Terminal Block 2 (AC Line) Connections, CE-3x2 5K-T

Terminal Block 2 is above the ignition battery. Connect the user-supplied wiring using a #1

flat-head screwdriver. Strip wires 3/8" (9.5mm) and torque to 7 in-lbs (0.8 Nm). Refer to the

table and photo below for alarm definitions.

Terminal Block 2

Pos # Function
23

Major Alarm NC

22

Major Alarm NO

21

Major Alarm Com

20

See Note

19

Alarm Bypass Com

18

Alarm Bypass NO

17

Alarm Bypass NC

16

Eng Run Com

15

Eng Run Com NO

14

Eng Run Com NC

13

Minor Alarm NO

12

See Note

11

Minor Alarm COM NO

10

Door NO

9

Door COM

8

LPG Monitor PWR (-12V)

7

LPG Monitor PWR (+12V)

6

AC Line Fail NC

5

AC Line Fail NO

4

AC Line Fail COM

3

AC Input Ground

2

AC Input Neutral

1

AC Input Line 1

1A

AC Input Line 2

Table 3-1, Terminal Block 2 (TB2) Connections, CE-3x2 5K-T

For customers requiring a Normally Closed (NC) logic minor alarm, make connections to TB2 positions 12

and 20.

NOTE:

Fig. 3-21, Terminal Block 2 (TB2) Position 1, 5kW

Position 1