The Engine Control Module, continued

4.8 ECM DIP Switch and Fuse Configuration

The ECM PCB has an eight-position DIP switch (SW5) used to configure the generator

interface, APU output voltage (AC or DC), and utility voltage.
The GRI board has three fuses, F1, F2, and F3.

F2: 12V Output to

APU Fan and Enclosure

Gas Detector

(2A, 250V Slo-Blo)

Alpha P/N 460-205-10

F3: 120/240Vac Input

to ECM Logic Transformer

(250mA, 250V Slo-Blo)

Alpha P/N 460-166-10

SW5

F1: 12V Input from APU

(2.5A, 250V Slo-Blo)

Alpha P/N 460-204-10

GRI

ECM PCB

Fig. 4-5, SW5 and Fuse Locations

Table 4-3, Telecom Defaults

Telecom Defaults

Low DC Bus Level

Default 49V (2V/cell)

High DC Bus Level

Default to 57V (2.38V/cell)

Service Interval

Default 100 hours

Autotest Interval

Will auto set to 14 days when SW5-8 is set ON

Autotest Duration

Default 10 minutes

Start Delay

Default 180 seconds (3 minutes)

Shutdown Delay

Default 720 seconds (12 minutes)

Over-voltage Duration

Default 5 seconds