Never cut off the main power supply to the

unit, except for complete shutdown. When

power is cut off from the unit, any

compressors using crankcase heaters cannot

prevent refrigerant migration. This means

the compressor will cool down, and liquid

refrigerant may accumulate in the

compressor. Since the compressor is

designed to pump refrigerant gas, damage

may occur when power is restored.

Before unit operation, the main power

switch must be turned on for at least twenty

four hours for units with compressor

crankcase heaters. This will give the

crankcase heater time to clear any liquid

accumulation out of the compressor before it

is required to run.

Always control the system from the control

panel, never at the main power supply

(except for emergency or for complete

shutdown of the system).

The standard compressors must be on a

minimum of 4 minutes and off for a

minimum of 5 minutes. The cycle rate must

be no more than 6 starts per hour.

The variable capacity compressors must be

on a minimum of 3 minutes and off for a

minimum of 3 minutes. The cycle rate must

be no more than 10 starts per hour.

The chiller is furnished with a pressure

differential switch that is factory installed

between the chilled water supply and return

connections. This sensor must not be

bypassed since it provides a signal to the

unit controller that water flow is present in

the heat exchanger and the unit can operate

without the danger of freezing the liquid.

The compressor life will be seriously

shortened by reduced lubrication, and the

pumping of excessive amounts of liquid oil

and refrigerant.

Wiring Diagrams

A complete set of unit specific wiring

diagram in point-to-point form is laminated

in plastic and located inside the control

compartment door.

General Maintenance

When the initial startup is made and on a

periodic schedule during operation, it is

necessary to perform routine service checks

on the performance of the chiller. This

includes reading and recording suction

pressures and checking for normal sub-

cooling and superheat.

Scroll compressors are directional

and will be damaged by operation in

the wrong direction. Low pressure

switches on compressors have been

disconnected after factory testing.

Rotation should be checked by a

qualified service technician at startup

using suction and discharge pressure

gauges and any wiring alteration

should only be made at the unit

power connection.

CAUTION

Rotation must be checked on all

MOTORS AND COMPRESSORS of

three phase units. All motors, to

include and not be limited to pump

motors and condenser fan motors,

should all be checked by a qualified

service technician at startup and any

wiring alteration should only be made

at the unit power connection.

CAUTION