The quarter turn graduations on the sleeve,

with the scribed line on the stem provide an

approximate flow measurement.

Note: The valve is shipped in closed

position. The indicator on the plastic

sleeve is aligned with the vertical scribed

line on the stem.

Step 2. Record the size of the valve and

stem position using the flow indicator scale.

Calculate the percentage of valve opening

based on the number of rings at the fully

open position.

Valve Size 2-1/2 3 4 5 6

8 10 12

Number

of Rings

(valve fully

open)

5

5 6 9 10 12 18 28

Step 3. Measure and record the differential

pressure across the valve in the throttled

position.

Step 4. Locate percentage of valve opening

on the flow characteristic curve. For the

given valve, record the percentage of

maximum flow rate.

Step 5. Locate the differential pressure

determined for the valve in the throttled

position on the Flo-Trex Performance

Curve. Determine the flow rate for the

given valve size at this differential pressure.

Step 6. Calculate the flow rate of the valve

in the throttled position by multiplying the

flow rate (Step 5) by the percentage of

maximum flow rate (Step 4).

Example:

Valve size: 4 in.

Differential pressure is 5.4 ft

Number of open rings is 3.

From the table, the number of rings for the 4

in valve fully open is 6. Divide open rings

by total, 3/6 = 50% throttled

From the Flo-Trex performance curve, a 4

in. valve with 5.4 ft of pressure drop

represents a flow of 400 Usgpm