Appendix - water piping component information, Water pressure relief valve, Automatic air vent valves – AAON LC-054 User Manual

Page 27

Advertising
background image

27

Appendix - Water Piping Component Information

Water Pressure Relief Valve

Overview

ASME Rated, Design Certified and Listed

by C.S.A

.

Used for protection against excessive

pressure on domestic storage tanks or tank-

less water heaters, the pressure relief valve

has no temperature relieving element.

Standard setting is 125 psi Size 3⁄4” x 3⁄4”

(20mm x 20mm). ASME construction and is

tested, listed and certified by the National

Board of Boiler and Pressure Vessel

Inspectors.

ANSI Z21.22 “Relief Valves for Hot Water

Supply Systems.”

DESIGN CERTIFIED and listed by C.S.A.

Automatic Air Vent Valves

Automatic Air Vent Valves provide air

venting for hot or cold water distribution

systems. These vents purge air that may be

in the water system.

The vent valve utilizes an internal baffle

system. The baffles slow water so that

entrapped air can separate. Once the air is

separated, the air migrates to the top of the

scoop chamber. The air is vented through

the factory installed vent.

Overview

Air scoops are constructed of one piece cast

iron. Baffles are engineered to separate air

from water. All air scoops come with 1/8”

vent connection. An additional stainless

steel expansion tank connection is available

on the 1-1/2” to 4” air scoops. Air scoops

never require servicing. The high point vent

should be turned clockwise one to two

rotations to allow proper air venting. It is

not recommended to remove the cap as dirt

and debris may enter the water system.

Air scoops are suitable for use with water or

water/glycol systems.

Operating Range

Maximum operating pressure:

125 psi (862 kPa)

Maximum operating temperature:

300ºF (135ºC)

Recommended Flow Rate:

4 ft. / sec.

Maximum Flow Rate:

8 ft. / sec.

Advertising