Noise Levels

Estimated Pumping Unit Sound Power Level, (Decibels), A-Weighted, at 1 m (3 ft.) from unit.

Vibration Levels

Vertical In-Line pumps are designed to meet vibration levels set by Hydraulic Institute Standard

HI Pump Vibration 9.6.4. Standard levels are as detailed below:

Dual Pump Specific Information

Dual Pump Flapper Valve Operating

Instructions

This unit is fitted with internal valves to

allow isolation of one pump for service and

to automatically prevent recirculation of the

flow when only one pump is running.

Procedure for Parallel or Stand-By

Pumping:

Discharge and suction valve stems should be

locked in the center position. This is

indicated by both locking handles in the

vertical position and the center pin of the

locking arms (4) locked by the handles. This

procedure allows the discharge flapper

valves to pivot freely and locks the suction

valve firmly in the center position.

Procedure for Isolation of One Side:

1. Stop the pump to be serviced.

2. Close and lock the suction and discharge

valves: as per instructions below.

3. Ensure seal flush line interconnection

valve is closed and drain the isolated casing.

4. Service isolated pump as required.