may be experienced, steps should be taken

to minimize contact or warn operators/users

that normal operating conditions will be

exceeded. In certain cases where the

temperature of the pumped liquid exceeds

the above stated temperature levels, pump

casing temperatures may exceed

100°C/212°F and not withstanding pump

insulation techniques appropriate measures

must be taken to minimize risk for operating

personnel.

Storage

Pumps removed from service and stored,

must be properly prepared to prevent

excessive rusting. Pump port protection

plates must not be removed until the pump is

ready to connect to the piping. Rotate the

shaft periodically (At least monthly) to keep

rotating element free and bearings fully

functional.

For long term storage, the pump must be

placed in a vertical position in a dry

environment. Internal rusting can be

prevented by removing the plugs at the top

and bottom of the casing and drain or air

blow out all water to prevent rust buildup or

the possibility of freezing. Be sure to

reinstall the plugs when the unit is made

operational. Rust proofing or packing the

casing with moisture absorbing material and

covering the flanges is acceptable. When

returning to service, be sure to remove the

drying agent from the pump.

Handling Large VIL Units

One effective way of lifting a large pumping

unit is to place lifting hooks through the

motor lifting rings or straps around the

upper part of the motor. The pump and

motor unit will free-stand on the casing ribs.

Remove the coupling guard and place (2)

lifting straps through the pump/motor

pedestal, one on each side of the motor shaft

and secure to the lifting device.

With the straps in place, using a spacer bar if

necessary to protect the motor fan cover, the

whole assembly can now be lifted securely.

Note: Handling, transportation and

installation of this equipment should only

undertaken by trained personnel with proper

use of lifting equipment.

Remove coupling guard and place lifting

straps on each side of coupling, use spacer

bar if necessary to protect motor fan cover.

Vertical Inline Pump Lifting Strap

Positioning:

Note:

All split-coupled pumps contain a tapped

hole in the motor bracket above the

discharge flange for draining the well. Pipe

this drain hole to a floor drain to avoid

overflow of the cavity caused by collecting

chilled water condensate or from seal

failure.