Startup

(See back of the manual for startup form.)

Before startup of the chiller make sure that

the following items have been checked.

1. Verify that electrical power is available

to the unit.

2. Verify that any remote stop/start device

connected to the chiller controller is

requesting the chiller to start.

3. Verify that liquid flow is present through

the chiller from the building.

4. There should be a building load of at

least 25% of the chiller capacity in order

to properly check operation.

5. With the main power switch off, review

the Controller Manual provided with the

chiller. Understand the keypad functions,

how to set the leaving water temperature

setpoint and how to initiate the Run

State.

Use the general check list at the top of the

startup form to make a last check that all the

components are in place, water flow is

present, and the power supply is energized.

Using the controller keypad, individually set

the outputs in “Manual On” to confirm relay

closure and compressor operation.

Cycle through all the compressors to

confirm that all are operating within

tolerance.

While performing the check, use the startup

form to record observations of amps and

refrigerant pressures.

When all is running properly, place the

controller in the Run mode and observe the

system until it reaches a steady state of

operation.

Note: For more information on

programming the controller refer to the

MCS Controller manual provided with the

unit.

Rotation must be checked on all

MOTORS AND COMPRESSORS of

three phase units. All motors, to

include and not be limited to pump

motors and condenser fan motors,

should all be checked by a qualified

service technician at startup and any

wiring alteration should only be made

at the unit power connection.

CAUTION

Before completing installation, a

complete operating cycle should be

observed to verify that all

components are functioning properly.

CAUTION

Electric shock hazard. Shut off all

electrical power to the unit to avoid

shock hazard or injury from rotating

parts.

WARNING

Improper installation, adjustment,

alteration, service or maintenance

can cause property damage,

personal injury or loss of life.

Installation and service must be

performed by a trained, qualified

installer.

WARNING

Advertising