From the flow characteristic curve, a 4 inch

valve at 50% open represents 34% of

maximum flow.

The approximate flow of a 4 inch valve with

a 5.4 ft pressure drop when 50% throttled is:

100

34)

x

(400

=136 US gpm;

100

34)

x

(25.2

=8.57 L/s

Note: To prevent premature valve failure it

is not recommended that the valve operate in

the throttled position with more than 25 ft

pressure differential. Instead the pump

impeller should be trimmed or valves

located elsewhere in the system to partially

throttle the flow.

Operation

To assure tight shut-off, the valve must be

closed using a wrench with 25 to 30 ft-lbs of

torque.

To assure trouble free check valve operation

and shut-off operation, the valve should be

periodically opened and closed to keep valve

seat and valve disc guide stem from

accumulating system contaminants.

Repacking of Flo-Trex valve under full

system pressure

If it is necessary, the stem O ring can be

changed under full system pressure.

Step 1. Record the valve setting.

Step

2.

Turn the valve stem

counterclockwise until the valve is fully

open and will not turn any further. Torque

to a maximum of 45 ft-lbs. This will ensure

good metal to metal contact and minimal

leakage.

Step 3. The valve bonnet may now be

removed. There may be a slight leakage, as

the metal to metal backseating does not

provide a drip-tight seal.

Step 4. Clean exposed portion of valve stem

being careful not to leave scratches.

Step 5. Remove and replace the O ring

gasket.

Step 6. Install the valve bonnet.

Step 7. Tightening the valve bonnet is

necessary to stop any leaks.

Step 8. Open valve to balance set point as

recorded in Step 1.

Note: On valve sizes of 2-1/2 inch and 3

inch, the full open position is 5 turns, though

the valve will open to 5-1/2 turns which is

just back of seating of valve.

Seat Replacement:

Step 1. Drain the system and remove valve

from piping.

Step 2. Remove the body bolts from the

body using an Allen Key.

Step 3. Remove seat and O Ring. O rings

are not used on valves of 8 inches or larger.

Step 4. Inspect and clean O ring cavity and

install new O ring and seat. Valve disc stem

should be inspected and replaced if worn.

Valve stem O ring should be replaced at this

time as discussed under Repacking of Flo-

Trex section.

Safety glasses should be worn.

CAUTION