Dual Pumps

When redundant pumping is required, a

factory installed dualArm pump can be

ordered on units 15 tons and larger. A

dualArm pump is a pump with two

independent motors and pumps in a single

casing. This pump has a swing split-flapper

valve in the discharge port to prevent liquid

recirculation when only one pump is

operating. Isolation valves in the casing

allow one pump to be isolated and removed

for service while the other pump is still

operating.

The controls package will activate the pump

when the unit is given a run command. If the

controls do not recognize flow in 60

seconds, the second pump will be activated

and an alarm signal will be generated. If the

second pump does not activate, the cooling

will be locked out.

Differential Pressure Gauge and

Thermometers

A differential pressure gauge and

thermometers are available as a factory

installed option when using a factory

installed pumping package. Thermometers

are installed around the evaporator of the

unit. A differential pressure gauge is

installed at each pump. This pressure gauge

is connected in three places to the water

piping: before the suction guide/strainer,

after the suction guide and before the pump,

and after the pump. There is also a needle

valve at each of these points to isolate the

pressure. To measure the pressure at any

given point, open the needle valve at that

point and close the other two needle valves.

Instead of two pressure gauges, one pressure

gauge is used to minimize calibration and

gauge errors.

Pipe Insulation

All evaporators in the LC Series chiller are

heat traced and insulated. The water piping

and components on standard LC are not heat

traced or insulated at the factory. The

factory can install heat trace as an optional

feature. All water piping shall be leak tested

in the field prior to startup, as shipping

vibrations may have loosened connections.

Installation

Lifting the Unit

If cables or chains are used to hoist the unit

they must be the same length and care

should be taken to prevent damage to the

cabinet or injury to the installer.

Arrange spreader bars, blocking, or other

lifting devices to prevent any damage to the

coils or the cabinet of the condensing unit.

Before lifting unit, be sure that all shipping

material has been removed from the unit.

All LC Series chillers have lifting channels

in the base of the equipment to allow

moving and placement without physical

damage.

Unit may be positioned with a forklift.

Remove the harness used in hoisting. Make

sure the unit is properly seated and level.

Locating the Unit

The LC Series chiller is designed for

outdoor applications and mounting at

ground level or on a rooftop. It must be

placed on a level and solid foundation that

has been prepared to support its weight.

When installed at ground level, a one-piece

concrete slab should be used with footings

that extend below the frost line. Also with

ground level installation, care must be taken

to protect the coil fins from damage due to

vandalism or other causes. As a standard, all