31

discharge gauge reading. Convert the result

into the units of the pump head as stated on

the pump nameplate and compare the

values. Should the actual pump operating

head be significantly less than the nameplate

head value it is typically permissible to

throttle the discharge isolation valve until

the actual operating head is equal to the

nameplate value.

Any noise or vibration usually disappears.

The system designer or operator should be

made aware of this soon as some adjustment

may be required to the pump impeller

diameter or drive settings, if applicable, to

make the pump suitable for the system as

installed.

Check rotation arrow prior to operating the

unit. The rotation of all Vertical In-Line

units is “clockwise” when viewed from the

drive end. (Looking from on top of / behind

the motor)

General Care

Vertical In-Line pumps are built to operate

without periodic maintenance, other than

motor lubrication on larger units. A

systematic inspection made at regular

intervals, will ensure years of trouble-free

operation, giving special attention to the

following:

Keep unit clean. Keep moisture, refuse, dust

or other loose particles away from the pump

and ventilating openings of the motor

Avoid operating the unit in overheated

surroundings (Above 100ºF/40ºC).

Any possibility of the unit starting while

being serviced must be eliminated.

If mechanical seal environmental

accessories are installed, ensure water is

flowing through the sight flow indicator and

that filter cartridges are replaced as

recommended.

Lubrication

Pump

Lubrication is not required. There are no

bearings in the pump that need external

lubrication service.

Motor

Follow the lubrication procedures

recommended by the motor manufacturer.

Many small and medium sized motors are

permanently lubricated and need no added

lubrication. Generally if there are grease

fittings evident the motor needs periodic

lubrication, and if there are no grease fittings

evident, no periodic lubrication is required.

Check the lubrication instructions supplied

with the motor for the particular frame size

indicated on the motor nameplate.

Mechanical Seal

Mechanical seals require no special

attention. The mechanical seal is fitted with

a flush line. The seal is flushed from

discharge of the pump casing on split-

Check rotation arrow prior to

operating the unit.

CAUTION

Electric shock hazard. Before

attempting to perform any service or

maintenance on pumping unit,

disconnect power source to drive,

LOCK IT OFF and tag with the

reason.