Pump Piping - General

Caution

The discharge valve only is to be used to

throttle pump flow, not the suction valve.

Care must be taken in the suction line layout

and installation, as it is usually the major

source of concern in centrifugal pump

applications

Alignment

Alignment is unnecessary on close-coupled

pumps as there is no shaft coupling.

Split-coupled units are accurately aligned at

the factory prior to being shipped and do not

need re-aligning when installed.

Operation

Starting Pump

Ensure that the pump turns freely by hand,

or with some mechanical help such as a

strap and lever on larger pumps. Ensure that

all protective guarding is securely fixed in

position.

The pump must be fully primed on start up.

Fill the pump casing with liquid and rotate

the shaft by hand to remove any air trapped

in the impeller. On split coupled units, any

air trapped in the casing as the system is

filled must be removed by the manual air

vent in the seal flush line. Close-coupled

units are fitted with seal flush/vent lines

piped to the pump suction area. When these

units operate residual air is drawn out of the

pump towards the suction piping.

Energize the motor momentarily and check

that the rotation corresponds with the

directional arrow on the pump casing.

To reverse rotation of a three phase motor,

interchange any two power leads.

Start the pump with the discharge valve

closed and the suction valve open, and then

gradually open the discharge valve when the

motor is at operating speed. The discharge

valve may be opened slightly at start up to

help eliminate trapped air.

When stopping the pump: Close the

discharge valve and de-energize the motor.

DO NOT run the pump against a closed

discharge valve for an extended period of

time (A few minutes maximum).

Star-Delta motor starters should be fitted

with electronic/mechanical interlocks that

have a timed period of no more than 40

milliseconds before switching from star

(Starting) to delta (Run) connection yet

allow the motor to reach full star (Starting)

speed before switching to delta (Run).

Should the pump be noisy or vibrate on

start-up a common reason is overstated

system head. Check this by calculating the

pump operating head by deducting the

suction pressure gauge value from the

Piping may carry high temperature

fluid.

CAUTION

Discharge valve only is to be used to

throttle pump flow.

CAUTION

Do not run pumps with discharge

valve closed or under very low flow

conditions.

CAUTION