Brooks – Brooks Instrument GF81 User Manual

Page 43

Advertising
background image

4-5

Brooks

®

GF40/GF80/GF81 Devices

Installation and Operation Manual
X-TMF-GF40-GF80-Series-MFC-eng
Part Number: 541B161AAG
June, 2013

Section 4 Maintenance & Troubleshooting

Symptoms & Possible Causes

Corrective Action

2. Flow out of range (Continuted).

Is the device zero correct?

Zero the device according to zeroing
procedure in Section 2-16. Verify leak check rates
are OK.

3. No gas control; flow is at or
above maximum.

Is the gas pressure across the device

Verify that the pressure is correct for the gas and

too high?

range. If required, adjust inlet/outlet pressure to
achieve proper pressure reading.

Are system valves open, or is the

Use tool software to verify.

purge input activated?

Confirm that pin 12 is not connected to an active voltage
source.

Is the setpoint correct for the

Use tool software to verify.

required flow?

4. No gas flow above some setpoint.

NOTE: When the setpoint is
increased beyond this point,
the

GF40/GF80/GF81

Series signal remains at

some value lower than the set-point.

Is the gas inlet/outlet differential

Verify that the pressure is correct for

pressure sufficient?

the gas and range. If required, adjust
regulator to achieve proper pressure.

NOTE: If the pressure is too low,
the valve voltage to the

GF40/GF80/GF81

Series

will be at its maximum output. This condition
will cause internal GF valve heating and
inability to properly reach desired flow setpoints.

Is the

GF40/GF80/GF81

Series calibrated for the

Check

GF40/GF80/GF81

Series side label. Run a flow check

gas flow?

to verify. If flow is incorrect, replace the

GF40/GF80/GF81

Series with a unit that is calibrated properly.

Table 4-2 GF40/GF80/GF81 Series Troubleshooting Guide (Continued)