3 - 28

How the Forward Limit functions is determined by the following Control Parameter:

Forward Limit Format (CP-37)

Use the Forward Limit Format (CP-37) parameter to determine how the
Forward Limit will function during “Run”. If you set CP-37 to "1", then
the M–Traverse will engage “F-Stop” when the Forward Limit is encoun-
tered during “Run”. However, if you want the M–Traverse to terminate
the Constant Pitch Plateau, decelerate to zero speed, process the
Forward End Dwell and then begin the reverse profile back to “Home”
when the Forward Limit is encountered, then set CP-37 to "2".

Table 3-20 Default Polarity Control Parameters

CP

Parameter Name

Parameter Value

CP-37

Forward Limit Format

1

Table 3-21 Entering Polarity Control Parameters

CP

Parameter Name

Parameter Value

CP-37

Foward Limit Format

Enter “1” to engage ”F-Stop”.

Enter “2” to terminate the

Constant Pitch Plateau,

decelerate to zero, process

the dwell and begin the

reverse profile.