The Class 3400 meter can be used with two types of current sensors:

1. Split-core current sensor. This sensor opens so that it can be attached around

the circuit being monitored without interrupting power. Unless otherwise speci-

fied, all Class 3400 meters are supplied with this sensor type.

2. Solid-core current sensor. This sensor does not open and requires the monitored

conductor to be removed from the circuit to install the current sensor. This type is

only supplied when specified at time of order.

6.4.1 Installing the Split-Core Current Sensor Assembly

1. Each phase being monitored will require one two-piece current sensor assembly.

Open the two-piece current sensor assembly by releasing the nylon clamp using

a flathead screwdriver.

Fig. 5. Split Core Sensor.

2. Reassemble the current sensor assembly around the conductor(s) to be moni-

tored. Ensure the current sensor halves marked “Load” are both facing the load

side of the conductor. The colored arrow will be on the source side of the con-

ductor being monitored and MUST be pointed in a clockwise direction around the

conductor being monitored. Tighten the nylon clamp to complete the assembly.

Fig. 6. Split Core Sensor.

IMPORTANT:

When looking from the source side of the conductor(s) being monitored, you

should see the arrow on the current sensor assembly. The arrow should be

pointing in a clockwise direction around the conductor(s) being monitored. If

the arrow is not positioned on the source side, inaccurate readings will result.