6.10 Modbus RTU Wiring

The Class 3400 Modbus meter communicates with building automation equipment

over a 2-wire (3-conductor) RS-485 network using Modbus RTU protocol. The meters

are networked in a daisy-chain configuration (Section 6.7) with BELDEN 1120A cable

or equivalent. The cable rating of 600V allows the RS-485 network to be connected to

480-volt meters. Up to 52 meters can be installed on a network string. The maximum

combined length of all daisy-chained cables must not exceed 4000 feet.

The meter-to-network connection is through the 3-screw terminal which is located on

the Main Power Board of the meter.

Fig. 14. Modbus RTU Wiring.

The meter is shipped with a Modbus ID number of 01. This must be changed if the

network has more than one meter installed. The change must be done before the

meter is introduced into the network. The meter can be numbered from 1 to 247. There

can be no duplicate numbers on a network, so caution must be taken when assigning

a meter ID number prior to its installation on the RS-485 network.

SEE SECTIONS 10 AND 11 FOR INSTRUCTIONS ON CHANGING I.D. AND IP

ADDRESSES.