3.0 METER TECHNICAL SPECIFICATIONS

(CONTINUED)

Input Voltage

Configuration

3-wire (Delta) Or 4-wire (Wye)

Mains Voltage Input Up To 600 VAC RMS Available
Input Power

6 VA Maximum Rating

Current Sensor

Rating

Up To 3200 Amps RMS AC Available

Power Factor

0.5 Leading Or Lagging

Line Frequency

50-60 Hz

Metering Accuracy

ANSI C12.20

Voltage Operating

Range

+/-10% Of Rated Load

Temperature Range -20 C To +50 C (Standard indoor enclosure):
Relative Humidity

Range

0-95% Non-condensing

Altitude

2000 Meters Maximum

Voltage Overload

+25% Continuously: +100% For 20 Cycles

Current Sensor

Overload

100% For 1 Minute Without Damaging Meter

Pollution Degree

Degree 2 In Accordance With IEC 664

Installation

(Overvoltage)

Category

Category III

Measurement

Category

Category III

Enclosure Material

UL Type 1 or Type 4X

Display Readout

4-line LCD

Standard Ranges

4-Wire Wye 208 VAC: 100, 200, 400, 800,1600 Amp

3-Wire Delta240 VAC: 100, 200,400,800,1600 Amp

4-Wire Wye 480 VAC: 100, 200, 400, 800,1600 Amp

3-Wire Delta480 VAC: 100, 200,400,800,1600 Amp

4-Wire Wye 600 VAC: 100, 200, 400, 800,1600 Amp

Modem Interface

Cable:

UL-listed/rated telephone

cord, 4-conductor, 300 VAC,

stranded conductors 22-26

AWG.

Cable Connector:

RJ-11 IDC termination

Ckt Input Isolation

5.3K VAC

Baud Rate:

9600