CLASS 3400 METER
43
62-0391-01
13.0 FREQUENTLY ASKED QUESTIONS
(CONTINUED)
Q. The load I need to monitor has parallel feeds. How do I install the current sensors
for this application?
A. There are two ways you can monitor parallel feeds. The easiest and preferred
method is to clamp the sensors around all feed wires for each phase. The second way
to monitor parallel feeds is to clamp the sensor around one of the feed wires for each
phase. When you read the meter, the final reading must be multiplied by the number of
feed wires for each phase.
Q. I have two subpanels I would like to monitor with one Class 3400 meter. These
subpanels are fed by different transformers in the building. Can I parallel sensors and
monitor both panels with one meter?
A. No. These panels cannot be monitored with one meter because they are different
power sources. When you parallel current sensors, all loads being monitored must be
from the same voltage source.
Q. I have 5 breakers in one subpanel I would like to monitor with one class 3400 meter.
Can this be done without having to parallel current sensors?
A. Yes. Simply run all the breaker wires through one set of current sensors. Make sure
all A-phase circuits are run through the A-phase sensor, and the same for B & C
phases. The meter should be sized by the highest amount of current being monitored
by one sensor.
Q. I’ve gone through the troubleshooting guides and I still can’t get my class 3400
meter to work. What should I do?
A. Before removing the unit, contact E-Mon’s technical services department at (800)
334-3666. E-Mon’s technical department will assist you in detailed troubleshooting of
the meter installation and assist you in getting the unit running without having to
remove and/or return it.