E-Mon E34-6003200R*KIT User Manual

Page 47

Advertising
background image

CLASS 3400 METER

47

62-0391-01

41 Analog Input Reserve C
42* Analog Input External Input 1

Pulse

Present Value R

43* Analog Input External Input 2

Pulse

Present Value R

*External inputs are standard on Class 5000 meters and optional on Class 3400 meters (Part of Expanded

Feature Package).

Lonworks SNVT Types Point Map:

Network Variable

Name

SNVT Type

Description

Units

CL3400

nvoKWh_Del

SNVT_count_inc_f Energy delivered

kWh

R

nvoKWh_Rec

SNVT_count_inc_f Energy received

kWh

R

nvoKVarh_Del

SNVT_count_inc_f Reactive energy

delivered

kVARh R

nvoKVarh_Rec

SNVT_count_inc_f Reactive energy

received

kVARh R

nvoReal_Pwr

SNVT_count_inc_f Real power

kW

R

nvoReact_Pwr

SNVT_count_inc_f Reactive power

kVARh R

nvoAppar_Pwr

SNVT_count_inc_f Apparent power

kVARh R

nvoPwr_Fact

SNVT_pwr_fact_f

Power factor

% PF

R

nvoCurrent_Total

SNVT_amp_f

Current total

Amps

R

nvoCurrent_Avg

SNVT_amp_f

Current average

Amps

R

nvoVolt_LN

SNVT_volt_f

Voltage line-neutral

Volts-N R

nvoVolt_LL

SNVT_volt_f

Voltage line-line

Volts-L R

nvoFrequency

SNVT_freq_f

Frequency

Hz

R

nvoPhase_Angle

SNVT_angle_f

Phase angle

Degree R

nvoReal_Pwr_PhA

SNVT_count_inc_f Real power, phase A kW

R

nvoReal_Pwr_PhB

SNVT_count_inc_f Real power, phase B kW

R

nvoReal_Pwr_PhC

SNVT_count_inc_f Real power, phase C kW

R

nvoReact_Pwr_PhA

SNVT_count_inc_f Reactive power,

phase A

kVAR

R

nvoReact_Pwr_PhB

SNVT_count_inc_f Reactive power,

phase B

kVAR

R

nvoReact_Pwr_PhC

SNVT_count_inc_f Reactive power,

phase C

kVAR

R

BACnet Object Descriptors:

ID

BACnet

Object

Description

Units

BACnet

Property

CL

3400