Warning, 0 preventative/scheduled maintenance, 0 lithium battery replacement – E-Mon E34-6003200R*KIT User Manual

Page 32

Advertising
background image

CLASS 3400 METER

62-0391-01

32

8.0 PREVENTATIVE/SCHEDULED

MAINTENANCE

The unit is shipped in a calibrated and fully functional tested condition. Since the unit is

factory-calibrated using proprietary firmware algorithms, no internal unit adjustments

are necessary.

This unit contains no internal adjustments, so no preventative or scheduled

maintenance is required.

No cleaning or decontamination procedures are required for this instrument.

9.0 LITHIUM BATTERY REPLACEMENT

The Class 3400 kWh/Demand meter has a Lithium Battery Cell, which is used to retain

the contents of SRAM and the RTC during power outages. The battery has a life

expectancy of greater than 5 years.

Fig. 18. Battery Specifications at 25 Degrees Celsius.

WARNING

Only replace battery with Panasonic part number CR2032 only. Use of another

battery may present a risk or explosion. See owners manual for safety

instructions. Internal circuit card components are extremely sensitive to

electrostatic discharge. Be careful not to touch internal circuitry prior to

discharging any static buildup on your person. To discharge yourself, touch a

grounded metal object such as conduit or a metal enclosure exterior.

The battery cell is mounted in a coin cell on the upper right side of the main

power board. Replace the battery if the low battery warning is on display.

Nominal Working Voltage

3 Vdc Output

Nominal Current Capacity

225 mAHr

Cell Chemical

Manganese Dioxide Lithium

Operating Temperature Range

-30 to +60 Degrees Celsius

Manufacturer

Panasonic

Manufacturer’s Part Number

CR2032

Advertising