1 expansion board connections, Io - terminals relay - terminals, Class 3400 meter – E-Mon E34-6003200R*KIT User Manual

Page 39

Advertising
background image

CLASS 3400 METER

39

62-0391-01

12.1 Expansion Board Connections

* The input terminals are used with “dry” contacts from third party metering devices.

They can be used with mechanical or electronic contacts. If using electronic contacts,

be sure to maintain polarity as shown. Maximum pulse frequency is 10Hz. The output

terminals are rated for a maximum of 40 volts AC or DC. The maximum load is 400 ma.

** The relay terminals are rated for a maximum of 250 VAC and a load of 3 amps.

Relay #1 is set through the push buttons on the display board. Relay #2 is only

accessed through special software commands. See Section 12.3 for details on setting

relay #1.

M33321

+

INP1

+

+

+

INP2

OUT1

OUT2

NC COM2 NO

NC COM1 NO

IO - Terminals

Relay - Terminals