CLASS 3400 METER

62-0391-01

38

12.0 CLASS 3400 METER EXPANSION

BOARD

The Class 3400 Meter Expansion Board option adds a number of new features to the

meter.

Pulse Input

The board contains two pulse inputs for connection to external metering devices which

have a dry-contact type of output pulse. The maximum frequency of pulses accepted

by the Class 3400 meter is 10Hz.

Pulse Output

The board contains two pulse outputs for use by Building Automation Systems, etc.

One pulse is in watt-hours, the second pulse is in VAR-hours. They are not polarity

dependant. The maximum current allowed is 400ma and the maximum voltage allowed

is 40 VAC or VDC.

Alarm Relay / Load Control

There are two form “C” relays on the expansion board. They are designed to be used

for alarming or load control functions on circuits up to 250VAC and 3 amps.