CLASS 3400 METER

62-0391-01

20

6.7 RS-485 Wiring (continued)

After performing these steps, all of the meters will be connected in a daisy chain

configuration. This network of meters can then be connected to the RS-485 network

and communication can be established.

Internal Modem

An optional internal modem inside one meter will communicate with the others via the

RS-485 network. Simply connect one of the two telephone jacks on the modem to the

telephone line to complete the installation.

Local Computer

A local computer installed in the building can communicate with the RS-485 network.

The computer must be connected to an RS-232 key. The RS-232 key is then

connected to an available RS-485 jack in the meter using an RJ-11 cable.

NOTE: Don’t confuse the modem’s telephone jacks with the RS-485 jacks!!!

NOTE: When using one meter with an internal modem, only the telephone line is

connected. RS-485 is not needed.

6.8 RS-232 Communications

6.8.1 Hardwired System using the RS-232 Communication Key

The RS-232 communications key allows you to connect Class 3400 meters to a

personal computer that has the E-Mon Energy™ software installed. The computer

communicates with the meters through the RS-232 key.

The RS-232 key must be located within 15 feet of the host computer.