0 meter technical specifications – E-Mon E34-6003200R*KIT User Manual

Page 7

Advertising
background image

CLASS 3400 METER

7

62-0391-01

3.0 METER TECHNICAL SPECIFICATIONS

Ordering Information: Define brand, class, input voltage, current sensor rating,

enclosure, protocols/options, expanded feature package, and sensor type in the format

A-BB-CCC-DDDD-E-FF-G-HHH, where:

A = Brand: E for E-Mon, H for Honeywell

BB = designates Class: 3200 (32), 3400 (34), or 5000 (50) meter

CCC = input voltage: (208, 480, 600)

DDDD = current sensor rating: (100, 200, 400, 800, 1600, 3200)

E = enclosure: J = metal (type 1), R = non-metallic (type 4X)

FF= protocol/options:

G = Expanded Feature Package: package = X, no package = “blank”

(on Class 3400 only)

HHH= Sensor Type: kit=split-core, scs= solid-core, non-supplied blank”

RS-485

Ethernet

Option

01

EZ7

EZ7 Ethernet

None

02

Modbus RTU

EZ7 Ethernet

None

03

BACnet MS/TP

EZ7 Ethernet

None

04

EZ7

Modbus TCP/IP Ethernet

None

05

EZ7

BACnet IP Ethernet

None

06

Modbus RTU

Modbus TCP/IP Ethernet

None

07

Lonworks FT-10

EZ7 Ethernet

None

08

Lonworks FT-10

Modbus TCP/IP Ethernet

None

09

EZ7

EZ7 Ethernet

Modem

10

EZ7

Modbus TCP/IP Ethernet

Modem

11

EZ7

BACnet IP Ethernet

Modem

M33317

EXAMPLE:

E 34 208

400

R

05

X

CLASS 3400 METER

INPUT VOLTAGE (208V)

CURRENT RATING (400A)

ENCLOSURE (4X)

EZ7/BACnet IP/NO MODEM

E-MON

EXPANSION PACKAGE

KIT

SPLIT CORE SENSORS

Advertising