Caution, Warning, 0 introduction – E-Mon E34-6003200R*KIT User Manual

Page 4

Advertising
background image

CLASS 3400 METER

62-0391-01

4

1.0 INTRODUCTION

The E-Mon D-Mon® Class 3400 meter is a 3-element meter with communications. The

device is used to monitor electric power usage of individual loads after the utility meter

and store kW and kVAR data for automatic meter reading. The Class 3400 meter is

dual protocol capable and provides both RS485 and Ethernet communications.

Installation must only be performed by qualified personnel and in accordance with

these instructions and all applicable local and national electrical codes. E-Mon and its

representatives assume no responsibility for damages or injury resulting from the

improper installation of this meter.

Verify the input voltage rating and configuration on the unit panel label to ensure that it

is suitable for the intended electrical service. Class 3400 meters labeled for 120/208V

service MUST NOT be installed on service feeds of 277/480 volts or 347/600 and vice

versa.

Verify that the Class 3400 meter’s current sensors are sized suitably for the load to be

monitored. Compare the color of the arrows on the current sensors to the chart below

to confirm the correct current sensor is being used.

CAUTION

Internal circuit card components are extremely sensitive to electrostatic

discharge. Prior to handling or touching internal circuitry, discharge any static

buildup on your person. To discharge yourself, touch a grounded metal object

such as conduit or an earth grounded metal enclosure.

WARNING

Use of this instrument, the E-Mon D-Mon Class 3400, in a manner inconsistent

with this manual or not specified by the manufacturer in writing, can cause

permanent damage to the unit and/or serious injury to the operator. The

protection and safety features provided by this equipment may become

impaired or otherwise compromised.

NOTE: If any trouble arises during installation or functional verification operations, do

not immediately remove unit. Before removing the unit, contact E-Mon’s tech-

nical support department at (800) 334-3666. E-Mon’s technical department

will assist you in detailed troubleshooting of the Class 3400 installation and

assist you in getting the unit operating correctly.

Sensor Arrow Color Code

Sensor Rating

Brown

100 A

Red

200 A

Yellow

400 A

Black

800 A

Blue

1600 A

White/Black 3200

A