CLASS 3400 METER

62-0391-01

24

6.9.2 External Modem

1. All meters should be connected to the RS-232 key as described in 6.8.2.

2. DISCONNECT POWER TO THE RS-232 KEY. Remove the cover by removing

the 2 screws from the bottom of the enclosure.

3. On the circuit board, locate the blue jumpers J7 (MODEM) and J8 (ex-MODEM).

If these jumpers are set in the DIRECT position, you must move the jumpers so

they are set in the MODEM position. Replace the cover and secure the enclo-

sure.

4. Connect the RS-232 key to the external modem using the supplied 8-conductor

flat modular cable.

5. Connect the 9VDC adapter to the power input on the back of the RS-232 key

and plug it into a 120VAC outlet.

IMPORTANT:

The modem should use a phone line that is dedicated exclusively to the AMR

system. Do not use a phone line that is shared by another modem or fax

machine.

6.9.3 Baud Rate Selection

The communication baud rate is selected by means of DIP switch S2 positions 3 and 4

on the circuit board. There are four (4) selections: 9600 (factory default), 19200,

38400, and 76800.

1. Select 9600 when using the Class 3400 meter with a modem.

2. The baud rate on the meter must always match the baud rate selected in the E-

Mon Energy software; otherwise, communications will not work.

3. After a baud rate change, press CPU Reset to register the change.

4. All meters in the daisy-chain circuit must be set at the same baud rate.

5. The DIP switch is located above the RS-485 terminals.

NOTE: USE ONLY POSITIONS 3 AND 4 - DO NOT CHANGE ANY OTHER

POINTS.