2 current sensor diagnostics – E-Mon E34-6003200R*KIT User Manual

Page 18

Advertising
background image

CLASS 3400 METER

62-0391-01

18

6.6.2 Current Sensor Diagnostics

The load current must be at least 1% of the meter’s rated load in order to use the

diagnostic function. Current sensor diagnostics can detect:

1. Reversed current sensors

2. Incorrect phase correspondence

3. Unusually low power factor (0.642 or lower)

CT Error: (ABC) is used to detect the swapping of current sensor phases. This

message could (in some rare cases) indicate a low (<65%) power factor condition. This

message may appear intermittently due to changes in line conditions. It should not be

on continuously. (See Section 6.4.1.)

NOTE: If you have connected the current sensor to all three terminals and the error

message is still appearing, reverse the black and white wires and repeat the

previous steps until the correct connection is found.

If the

CT Error:

message disappears, you have found the correct sensor connection;

however, the current sensor was not installed properly around the conductor, or the

sensor wires were extended and not spliced together correctly. Correct the sensor

installation, reconnect the black wire to the black terminal and the white wire to the

white terminal on the plug and reinstall the plug into the correct phase terminal for that

current sensor. The error message should disappear and the current sensor is now

installed properly.

If the

CT Error:

message does not disappear at any time while trying all 3 inputs both

ways, check the AC voltage input from the current sensor between the black and white

wires using an AC voltmeter. It will read approximately zero volts indicating that the

load current is very small (or zero) or the current sensors are not secured properly

(tight connection between core halves or lead splices not secure.)

Once the first current sensor is connected properly and the error message disappears,

repeat the previous procedure for the remaining two current sensors. When all error

messages have disappeared and all sensors are installed correctly, the meter is

operational.

Advertising