Commissioning – Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual

Page 11

Advertising
background image

Commissioning

‘Auto’ Alignment and ‘Set’ 0/100 (Calibrate)

9. ‘Set’ 0/100 (Calibrate)

• Select ‘Auto’ to automatically

align the infrared beam

• Signal Strength will be shown

during Alignment

• If the LASER is turned on it

will not necessarily be

pointing on the Reflector

after ‘Auto’ is run - this is

normal

8. ‘Auto’ Alignment

When ‘Set’ is displayed press

When ‘S-00’ is displayed, cover the Reflector with a non-

reflective material and leave covered, then press

When ‘S-01’ is displayed, uncover the Reflector and

leave uncovered, then press

Repeat Steps 5 to 9 for any other Detectors found during

the ‘Find’ process

11

LoA: 7 minutes

HiA: 4 minutes

0044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:38 Page 11