Approval Information

Territory-Specific Approval Information

European Approval Information

Complies with EN54-12 for sensitivity levels between 25%

and 35% with a maximum delay to fire of 20 seconds.

UL Approval Information

UL File Number: S3417

0832

Fire Fighting Enterprises Ltd, 9 Hunting Gate, Hitchin,

SG4 0TJ, UK

07

0832-CPD-0565

EN54-12

Line Detector using an Optical Beam

Fire Safety

Documentation: See doc. 0044-034

Distance between

Detector and Reflector

Fire Threshold

Range

8

10m (26.2

32.8ft)

10

18%

10

15m (32.8

49.2ft)

15

25%

15

22m (49.2

72.2ft)

15

35%

22

40m (72.2

131.2ft)

25

50%

40

60m (131.2

196.8ft)

35

50%

60

100m (196.8

328.1ft)

50%

All installations should comply with NFPA72