In Use

Cleaning the System

Cleaning the System

The system will automatically compensate for dust

build-up by changing the Compensation Level.

However, it is recommended that the Detector lenses

and the Reflector are cleaned periodically with a soft

lint-free cloth.

If the Compensation Level for a particular Detector

remains above 130 for several days, this indicates

that cleaning should take place on that Detector.

The system should be isolated from the Fire Control

Panel before cleaning takes place.

After cleaning, verify that the system is operating

normally:

If the Signal Strength is between 92% and 108%

- leave the system to compensate back to 100% (this

should take no more than 12 hours)

If the Signal Strength is above 108%

- reduce Compensation Level until Signal Strength is

92—108%, and wait for system to compensate back

to 100%

If the Signal Strength is below 90%

- perform LASER Targeting, Auto-Align, and Set.

How to change Compensation Level:

Use

to move between icons

in the Detector Menu, until this icon is
shown

15

0044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:39 Page 15