Troubleshooting

Error Codes

Detector Not Found
System Controller could not find

Detector. Also displayed during

power up.
• Wait 45 seconds for system to

power up

• Check wiring between System

Controller and Detector (Voltage

to Detector should be 11—13V)

Detector is connected but not

‘Found’
A Detector is connected but not

‘Found’
• Follow ‘Find’ process and

align if necessary

Compensation Level Not Zero
Compensation must equal zero

when ‘Set’ is selected.
• Re-align Detector using Auto-

Align

Signal Strength Out of Range
Signal Strength is too low or too high

after Auto-Align.
• Ensure correct distance has been

set

• Ensure correct Reflector type has

been used

• Ensure clear line of sight to

Reflector

• Re-align Detector using LASER

and Auto-Align

Reflector Not Found
Detector could not align with

Reflector
• Ensure correct distance has been

set

• Ensure correct Reflector type has

been used

• Ensure clear line of sight to

Reflector

• Re-align Detector using LASER

and Auto-Align

18

Auto-Align Failed
• Ensure correct distance between

Reflector and roof structures

• Ensure clear line of sight to

Reflector

• Re-align Detector using Auto-

Align