If it is not possible to see the LASER because of

the installation environment (for example, if you

cannot see the Reflector from the System

Controller or there is high ambient light) then use

‘Hand’ Alignment. This option displays the signal

strength value returned by the Detector, and

allows the user to move the beam

1. Start ‘Auto’ Alignment and press

after two

seconds to exit. (this will maximise infrared

power)

2. Select ‘Hand’ alignment

3. Use

to steer the beam until the

signal strength is above 800. There is no

auto-repeat function on any key. To move the

motor in any given direction more than once,

press the key multiple times

4. Cover the Reflector. If the Signal Strength

does not drop by more than half, the beam is

not aligned to the Reflector, so repeat Step 3

5. Perform ‘Auto’ alignment, followed by ‘Set’

Troubleshooting

LASER Not Visible

20

0044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:39 Page 20