System Information

Operating Parameters and Dimensions

Dimensions

Width, in (mm) Height, in (mm) Depth, in (mm) Weight, lb (kg)

Parameter

Description

Default

Parameter

Value

Pass code

User Code required to access Engineering Menu

1 2 3 4

Power Mode

‘Hi A’: System will operate at 50mA constant current

consumption

‘Lo A’: System will operate at 10,12,14,16 mA

constant current consumption (for 1, 2, 3 or 4

Detectors found)

‘LoA’

Compensation

Level

Range –49 to +204. Level of amplification applied to

compensate for dust build-up and building

movement At 75 Auto-Optimise is started

0

Transmit power Range 50 to 4095. Indicates the optical power

output. Set automatically by Auto-Align

-

Receive Gain

Range 1 to 255. Indicates the level of amplification

applied by the receiver

Set automatically by Auto-Align

-

Fire Threshold

Range 10% to 60%. Sets the amount of obscuration

required for the Detector to signal a Fire

35%

Delay to Fire

Range 2s to 30s. Sets the time the system needs to

be below the Fire threshold before signalling a Fire 10 seconds

Delay to Fault

Range 2s to 30s. Sets the time the system needs to

be below the Fault threshold before a Fault is

signalled

Note the signal needs to fall to <=13% within 2s

10 seconds

Distance

8—50m or 50—100m. Sets the distance between

Detector and Reflector. Affects the initial transmit

power at the start of Auto-Align

8-50m

Auto-Optimise

On/Off

Disables or enables Auto-Optimise (the automatic

beam movement function)

On

Latched/non-

latched

Sets if the system will latch Fire or automatically

reset Faults are always non-latching.

Non-

latching

System Controller, including base 8.0 (202)

9.1 (230)

3.2 (81)

2.2 (1.0)

Detector, including 'easy fit' base 5.3 (135)

5.3 (135)

5.3 (135)

1.1 (0.5)

Universal Bracket

5.3 (135)

5.3 (135)

2.8 (71)

0.4 (0.2)

Reflector (Single)

3.9 (100)

3.9 (100)

0.4 (10)

0.2 (0.1)

Operating Voltage

14—28V DC

Operating Current – Low Power Mode

10, 12, 14 or 16

mA ± 2mA (for 1,

2, 3 or 4 Detectors

found)

Operating Current – High Power Mode

48—52mA

Fire Threshold Range

0.45—3.98 dB

10—60%

Delay to Fire

2—30 s

Delay to Fault

2—30 s

Operating Distance between Detector and Reflector 8—100 m
Maximum angular misalignment of Detector

± 0.3 Deg

Maximum angular misalignment of Reflector

± 5 Deg

Maximum angular movement of Detector head

± 3.5 Deg

Optical wavelength

850 nm

Rapid Obscuration Fault threshold

87%

Operating Temperature (UL Approved)

0—+37.8 Deg C

Operating Temperature (EN54-12 Approved)

-10—+55 Deg C

Storage temperature

-40—+85 Deg C

Relative Humidity (non condensing)

93%

IP Rating

IP54

Relay Contact Voltage

30V DC

Relay Contact Current

100 mA

Maximum Cable Length (Controller to Detector)

100 m

Cable Gauge

24—14 AWG

0.5—1.5 mm

Housing Flammability rating

UL94 V0

29