Troubleshooting

Error Codes

Cannot Zero During ‘S-00’

in ‘Set’
The Reflector was not

covered or the Detector was

not aligned onto the Reflector.
• Ensure Reflector was

completely covered with a

non-reflective material

• Re-align Detector using

Auto-Align

No Signal During ‘S-01’ in ‘Set’
The Reflector was not uncovered

during ‘S-01’.
• Ensure Reflector was

uncovered when ‘S-01’ was

selected

‘Centre’ Stage of Alignment

Failed
Detector has aligned on

something other than the

Reflector
• Ensure clear line of sight from

Detector to Reflector for a

radius of 0.5m