Installation, Wiring diagrams – Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual

Page 5

Advertising
background image

Wiring Diagrams

Installation

Wiring for all other System Controllers (where more than one System

Controller is on one zone)

(Not to be used for UL region installations. Please refer to supplied CD

for UL region installation multiple-System Controller wiring)

Wiring for a single System Controller or last System

Controller on one zone

ZONE -

ZONE +

SUPPLY -

SUPPLY +

EARTH/SCREEN

Components not supplied (Check Fire Control Panel

manufacturer for values):

• Fire Resistor (Some Zone and Switch Interface

Modules do not need a Fire Resistor - replace Resistor

with a short circuit.)

• Detector Continuity Diode

• End Of Line (‘EOL’) component

• Check operation of Fire and Fault connection on Fire

Panel

• ALWAYS use a separate screened 2-core cable for

each detector head

• CAUTION: For system monitoring – Do not use

looped wire under any terminals. Break wire run to

provide monitoring of connections

Apply a

voltage of

5V to 40V

to ‘Ext

Reset’

contact for

at least 2

seconds to

clear a

Latched

Fire

condition

DET 1

DET 2

DET 3

DET 1

DET 2

DET 3

DET 4

14V - 28V DC

DET 4

14V - 28V DC

FIRE

ConA

1

2

3

N/O

Fire

Resistor

Fire

Resistor

Ext

Reset

Ext

Reset

EOL

COM N/C

N/O COM N/C

FAULT

ConB

1

2

3

FIRE

ConA

1

2

3

N/O COM N/C

N/O COM N/C

FAULT

ConB

1

2

3

5

0044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:38 Page 5