General Information

Installation

• Check the beam spacing against local regulations

• Position beam as high as possible, but with a minimum

distance of 0.5m from Detector to ceiling

• Mount Detector and Reflector directly opposite each

other

• Do NOT position Detector where personnel or objects

can enter the beam path

• Do NOT position 2 Detectors facing each other

• LED indicator must face downward

18—50m = 1

50—100m = 4

8—18m = 1

Use Short Range

Mask

50cm

8-100m

50cm

Ensure clear line of sight

from Detector to Reflector

Mount on solid surfaces (structural wall or girder)

50cm

50cm

8-100m

4