Alignment Status

10. System is Aligned

It is recommended to set the system back to ‘Lo A’ mode

Green LED on Detector will flash every 10 seconds, and

Signal Strength should be between 99% and 101%

Default values: 35% Fire Threshold, 10 second delay to

Fire and Fault, Non-Latching mode

Refer to User Guide page 13-14 to change settings and

for Fire and Fault Test

11. Check Alignment Status Displays

A commissioned

system will display:

When Detectors have

been found but the

selected Detector is not

aligned the system will

display:

When a Detector is

connected but not

‘Found’ the system will

display:

12