Commissioning – Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual

Page 12

Advertising
background image

Commissioning

Alignment Status

10. System is Aligned

• It is recommended to set the system back to ‘Lo A’ mode

• Green LED on Detector will flash every 10 seconds, and

Signal Strength should be between 99% and 101%

• Default values: 35% Fire Threshold, 10 second delay to

Fire and Fault, Non-Latching mode

• Refer to User Guide page 13-14 to change settings and

for Fire and Fault Test

11. Check Alignment Status Displays

A commissioned

system will display:

When Detectors have

been found but the

selected Detector is not

aligned the system will

display:

When a Detector is

connected but not

‘Found’ the system will

display:

12

0044-034-01 - THESEUS UG - ENGLISH:0044-003-01 User Guide.qxd 23/06/2009 08:38 Page 12