Settings and Final Tests

Detector Fire LED Test

Detector will signal Fire,

System Controller will stay

Normal.

Press

to exit

without performing the test

Relay/Controller Wiring Test

System Controller signals

‘Fire’ to Fire Control Panel

Press

or

to

exit

Software Fire Test

How to perform a Fire Test

from the System Controller,

to test the wiring to the Fire

Control Panel

NOTE: The Software Fire

Test is acceptable for Fire

Authority Acceptance and

Routine Maintenance per

UL268-5

Manual Fire and Fault Tests

After installation or cleaning, it is recommended that a manual Fire and Fault test is performed:

Fire Test: Cover the Reflector slowly so that it takes longer than

5 seconds to cover. The System Controller will signal Fire to the

Fire Control Panel

Fault Test: Cover the Reflector completely within 2 seconds. The

System Controller will signal Fault back to the Fire Control Panel.