IAI America RCM-GW-PR User Manual

Page 32

Advertising
background image



26

PfofiBus Gateway

a. Detail connection diagram

Details of SIO link connection are illustrated below. Controller link cables are available as options, but
the customer must provide the communication trunk.





























b. Producing a communication trunk

[1] Strip the sheath of a double shielded twisted-pair cable by

approx. 15 to 20 mm.

[2] Twist the shield wires and solder them onto the vinyl

wires of AWG22 or equivalent.

[3] Place a cable protection tube over the cable.
[4] Insert the core wires, without stripping them, into the

cable insertion holes in the connector (SDA, SDB,
GND, FG).

[5] With the cable inserted in the press-fit cable housing, apply

pressure from above to pressure-weld the core wires.

[6] Heat-treat the cable protection tube.

e-CON connector pin numbers





Always insert a terminal resistor (220

Ω, 1/4 W) at the end of the communication trunk

(between pins 1 and 2 of the e-CON connector).

Gateway Unit

Double shielded
twisted-pair cable
Recommended cable:
HK-SB/20276 X L
2P X AWG22 by Taiyo
Electric Wire & Cable

SIO communication trunk

4-way junction (5-1473574-4 by AMP)

e-CON connector (4-1473562-4 by AMP)

Housing color: Green

Controller link cable

Yellow

Orange

Blue

Yellow

Orange

Blue

e-CON connector (3-1473562-4 by AMP)

Housing color: Orange

Unit 1

Unit 2

Locking tab

e-CON connector

Apply pressure.

Cable tube

Double shielded twisted-pair shielded

Locking tab

Vinyl wire
(AWG22)

Solder

Shield
wire