IM 01C21B01-01E

2-4

2. HANDLING CAUTIONS

Note 2. Entity Parameters

• Intrinsically Safe Apparatus Parameters

[Groups A, B, C, D, E, F and G]
Vmax = 30 V

Ci = 22.5 nF

Imax = 165 mA

Li = 730

µ

H

Pmax = 0.9 W

* Associated Apparatus Parameters

(FM approved barriers)
Voc

30 V

Ca > 22.5 nF

Isc

165 mA

La > 730

µ

H

Pmax

0.9W

• Intrinsically Safe Apparatus Parameters

[Groups C, D, E, F and G]
Vmax = 30 V

Ci = 22.5 nF

Imax = 225 mA

Li = 730

µ

H

Pmax = 0.9 W

* Associated Apparatus Parameters

(FM approved barriers)
Voc

30 V

Ca > 22.5 nF

Isc

225 mA

La > 730

µ

H

Pmax

0.9 W

• Entity Installation Requirements

Vmax

Voc or Vt, Imax

Isc or It,

Pmax (IS Apparatus)

Pmax (Barrier)

Ca

Ci + Ccable, La

Li + Lcable

Note 3. Installation

• Barrier must be installed in an enclosure that meets

the requirements of ANSI/ISA S82.01.

• Control equipment connected to barrier must not use

or generate more than 250 V rms or V dc.

• Installation should be in accordance with ANSI/ISA

RP12.6 “Installation of Intrinsically Safe Systems for
Hazardous (Classified) Locations” and the National
Electric Code (ANSI/NFPA 70).

• The configuration of associated apparatus must be

FMRC Approved.

• Dust-tight conduit seal must be used when installed

in a Class II, III, Group E, F and G environments.

• Associated apparatus manufacturer’s installation

drawing must be followed when installing this
apparatus.

• The maximum power delivered from the barrier

must not exceed 0.9 W.

• Note a warning label worded “SUBSTITUTION OF

COMPONENTS MAY IMPAIR INTRINSIC
SAFETY,” and “INSTALL IN ACCORDANCE
WITH DOC. No. IFM012-A12 P.1 and 2.”

Note 4. Maintenance and Repair

• The instrument modification or parts replacement by

other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Intrinsically safe and Nonincendive
Approval.

F0203.EPS

Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G

EJA Series Pressure
Transmitters

EJA Series Pressure
Transmitters

Safety Barrier

Supply

Supply

Hazardous Location

Nonhazardous Location

Hazardous Location

Nonhazardous Location

General
Purpose
Equipment

+

+

+

+

+

+

[Intrinsically Safe]

Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.

Not Use
Safety Barrier

[Nonincendive]

General
Purpose
Equipment

b. FM Explosionproof Type

Caution for FM explosionproof type.

Note 1. Model EJA Series differential, gauge,

and absolute pressure transmitters with
optional code /FF1 are applicable for
use in hazardous locations.

• Applicable Standard: FM3600, FM3615, FM3810,

ANSI/NEMA250

• Explosionproof for Class I, Division 1, Groups B,

C and D.

• Dust-ignitionproof for Class II/III, Division 1,

Groups E, F and G.

• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60

°

C

• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA

Note 2. Wiring

• All wiring shall comply with National Electrical

Code ANSI/NEPA70 and Local Electrical Codes.

• When installed in Division 1, “FACTORY

SEALED, CONDUIT SEAL NOT REQUIRED.”

Note 3. Operation

• Keep the “CAUTION” nameplate attached to the

transmitter.
CAUTION: OPEN CIRCUIT BEFORE REMOV-
ING COVER. FACTORY SEALED, CONDUIT
SEAL NOT REQUIRED. INSTALL IN ACCOR-
DANCE WITH THE INSTRUCTION MANUAL
IM 1C22.