4 . INSTALLATION

4.5 Rotating Transmitter Section

The DPharp transmitter section can be rotated in 90

°

segments.

1) Remove the two Allen screws that fasten the

transmitter section and capsule assembly, using the
Allen wrench.

2) Rotate the transmitter section slowly in 90

°

seg-

ments.

3) Tighten the two Allen screws to a torque of 5 N·m.

IMPORTANT

Do not rotate the transmitter section more than
180

°

.

F0407.EPS

Vertical impulse piping type

Horizontal impulse piping type

Pressure-detector section

Transmitter section

Rotate 90

°

or 180

°

segments

Rotate 90

°

or 180

°

segments

Transmitter section

Pressure-detector section

Conduit connection

Conduit connection
Zero-adjustment screw

Figure 4.6

Rotating Transmitter Section

4.6 Changing the Direction of

Integral Indicator

IMPORTANT

Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area
before disassembling and reassembling an
indicator.

An integral indicator can be installed in the following
three directions. Follow the instructions in section 9.4
for removing and attaching the integral indicator.

F0408.EPS

Figure 4.7

Integral Indicator Direction