8. BRAIN TERMINAL BT200 OPERATION

(14) Bi-directional Flow Measurement Setup

(E30: BI DIRE MODE)

(a) This parameter enables selection of 50% output at

an input of 0 kPa.
Procedure is shown in the figure below.

(b) Combining this with

C40: OUTPUT MODE

provides a square root output computed indepen-
dently for 0% to 50% output and for 50% to 100%
output.

• Example: If measurement range is 0 to 10 kPa

(LRV=0 kPa, HRV=10 kPa)

The measurement range changes to –10 to 0 to 10 kPa

(output 0% to 50% to 100).

Note that “C21: LOW RANGE” and “C22: HIGH RANGE

are not changed.

ESC

SET
E30:BI DIRE MODE
OFF
< OFF >
< ON >

Use the or key

to select “ON.”

Press the key twice to

enter the setting.

F0829.EPS

20 mA (100% display)

4 mA (–100% display)

Output mode “LINEAR”

LRV

HRV

F0830.EPS

20 mA (100% display)

Low Cut

4 mA (–100% display)

Output mode “SQUARE ROOT”

LRV

HRV

(15) Range Change while Applying Actual

Inputs (H10: AUTO LRV, H11: AUTO HRV)

This feature allows the lower and higher range values
to be set up automatically with the actual input applied.
If the lower and higher range values are set,

C21:

LOW RANGE

and

C22: HIGH RANGE

are changed

at this same time.

Follow the procedure in the figure below.
The measurement span is determined by the higher and
lower range values. Changing the lower range value
results in the higher range value changing auto-
matically, keeping the span constant.

• Example 1: When changing the lower range

value to 0.5 kPa for the present

setting of 0 to 30 kPa, take the
following action with input pressure
of 0.5 kPa applied.

FEED

NO

OK

SET
H10:AUTO LRV
0.5000 kPa

DATA

DIAG

PRNT

ESC

PARAM
H10:AUTO LRV
0.5000 kPa
H11:AUTO HRV
30.500 kPa
H60:SELF CHEC
GOOD

ESC

SET
H10:AUTO LRV
0 kPa
+ 0

F0831.EPS

The higher range value is changed

keeping the span constant.

Parameters C21 and C22 are

changed at the same time.

Press the key twice.

The lower range value is changed

to 0.5 kPa.

Press the (OK) key.