9) operation mode setup, 10) impulse line connection orientation setup, 11) output status display/setup when a cpu failure – Yokogawa EJA110A User Manual

Page 49: 13) bi-directional flow measurement setup, Unit setup for displayed temperature -11, Unit setup for displayed static pressure -12

Advertising
background image

IM 01C21B01-01E

8-12

8. BRAIN TERMINAL BT200 OPERATION

(9) Unit Setup for Displayed Static Pressure

(D31: STAT.P.UNIT)

Follow the procedure below to change the static
pressure units.
Changing this parameter changes the unit for the

A30:

STATIC PRESS

(static pressure) display.

(10) Operation Mode Setup

(D40: REV OUTPUT)

This parameter allows the direction of the 4 to 20 mA
output to be reversed with respect to input. Follow the
procedure below to make this change.

• Example: Change 4 to 20 mA output to 20 to

4 mA output.

ESC

SET
D40:REV OUTPUT
NORMAL
< NORMAL >
< REVERSE>

Use the or key

to select REVERSE.

Press the key twice to

enter the setting.

F0825.EPS

(11) Impulse Line Connection Orientation

Setup (D45: H/L SWAP)

This parameter allows the impulse line connections to
be reversed at the transmitter. The parameter is not
applicable for capsule code V. Follow the figure below
to make this change.

• Example: Change the impulse line connection

from high pressure on right to high
pressure on left.

ESC

SET
D45:H/L SWAP
NORMAL
< NORMAL >
< REVERSE>

Use the or key

to select REVERSE.

Press the key twice to

enter the setting.

F0826.EPS

(12) Output Status Display/Setup when a CPU

Failure (D52: BURN OUT)

This parameter displays the status of 4 to 20 mA DC
output if a CPU failure occurs. In case of a failure,
communication is disabled.

Setting of HIGH or LOW is enabled. This is done with
the pin (CN4) on the CPU assembly. See Chapter 3 for
details.

Standard specifications
The parameter is set to HIGH. If a failure, the transmit-
ter outputs the signal of 110% or higher. The parameter

D53: ERROR OUT

is set to HIGH from the factory.

Optional code/C1
The parameter is set to LOW. If a failure, output which
is –5% or lower is generated. The parameter

D53:

ERROR OUT

is set to LOW from the factory.

• Example: Standard specifications

pin (CN4) position: H

D52: BURN OUT

HIGH

F0827.EPS

• Example: Optional code/C1

pin (CN4) position: L

D52: BURN OUT

LOW

(13) Output Status Setup when a Hardware

Error Occurs (D53: ERROR OUT)

This parameter allows the setting of the output status
when a hardware error occurs. The following three
selections are available.

(a) HOLD; Outputs the last value held before the error

occurred.

(b) HIGH; Outputs an output of 110% when an error

has occurred.

(c) LOW; Outputs an output of –5% when an error has

occurred.

Note: A hardware error means CAP MODULE FAULT of Er.01 or

AMP MODULE FAULT of Er. 02 which are shown in 8.5.2
“Errors and Countermeasures.”)

• Example: Set the output status to LOW when

a hardware error occurs.

ESC

SET
D53:ERROR OUT
HIGH
< HIGH>
< LOW>
< HOLD>

Use the or key

to select “LOW.”

Press the key twice to

enter the setting.

F0828.EPS