9.5.2 Troubleshooting Flow Charts

Connect BRAIN TERMINAL and check self-diagnostics.

Does the self-diagnostic

indicate problem location?

Contact Yokogawa service personnel.

F0907.EPS

The following sorts of symptoms indicate that transmitter
may not be operating properly.
Example : • There is no output signal.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
inferred for process variable.

Is power supply

polarity correct?

Are power

supply voltage and load

resistance correct?

Refer to error message summary in
Subsection 8.5.2 to take actions.

Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.

Fix pressure leaks, paying particular
attention to connections for impulse
piping,pressure-detector section, etc.

Fully close equalizing valve, and fully
open high pressure and low pressure
valves.

Refer to Section 6.6 for rated voltage
and load resistance.

Find/correct broken conductor or
wiring error.

Are valves opened or

closed correctly?

Is there any pressure leak?

Is there

continuity through the

transmitter loop wiring?

Do the loop numbers

match?

YES

NO

YES

NO

NO

YES

NO

NO

YES

YES

NO

YES

Connect BRAIN TERMINAL and check self-diagnostics.

Does the self-

diagnostic indicate problem

location?

Contact Yokogawa service personnel.

F0908.EPS

Is power supply

polarity correct?

Are valves opened or

closed correctly?

Refer to error message summary in
Subsection 8.5.2 to take actions.

YES

NO

NO

YES

Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.

Refer to individual model user manuals
and connect piping as appropriate for
the measurement purpose.

Fix pressure leaks, paying particular
attention to connections for impulse
piping, pressure-detector section, etc.

Fully close equalizing valve, and fully
open high pressure and low pressure
valves.

NO

YES

YES

NO

YES

Adjust the zero point.

NO

NO

YES

Is there any pressure leak?

Is impulse piping

to high pressure and low

pressure side correct?

Is zero point

adjusted correctly?

Output travels beyond 0% or 100%.