4 . INSTALLATION

4.

INSTALLATION

4.1 Precautions

Before installing the transmitter, read the cautionary
notes in Section 2.4, “Selecting the Installation
Location.” For additional information on the ambient
conditions allowed at the installation location, refer to
Subsection 10.1 “Standard Specifications.”

IMPORTANT

• When welding piping during construction, take

care not to allow welding currents to flow
through the transmitter.

• Do not step on this instrument after installation.

4.2 Mounting

᭿ The distance between the impulse piping connection

ports is usually 54 mm (Figure 4.2.1). By changing
the orientation of the process connector, the
dimension can be changed 51 mm or 57 mm.

᭿ The transmitter is shipped with the process connec-

tion, according to the ordering specifications. To
change the orientation of the process connections,
refer to Section 4.3.

᭿ The transmitter can be mounted on a nominal 50

mm (2-inch) pipe using the mounting bracket
supplied, as shown in Figure 4.2.2 and 4.2.3. The
transmitter can be mounted on either a horizontal or
a vertical pipe.

᭿ When mounting the bracket on the transmitter,

tighten the (four) bolts that hold the transmitter with
a torque of approximately 39 N·m {4kgf·m}.

57 mm

54 mm

51 mm

F0401.EPS

Figure 4.2.1 Process Connector Impulse Piping Connec-

tion Distances

Horizontal pipe mounting

Vertical pipe mounting

Transmitter
mounting bolt

U-bolt nut

Mounting bracket

U-bolt nut

Mounting bracket

50 mm(2-inch) pipe

50 mm(2-inch) pipe

U-bolt

U-bolt

F0402.EPS

Transmitter
mounting bolt

Figure 4.2.2 Transmitter Mounting (Horizontal Impulse

Piping Type)