5. WIRING

5.

WIRING

5.1 Wiring Precautions

IMPORTANT

• Lay wiring as far as possible from electrical

noise sources such as large capacity transform-
ers, motors, and power supplies.

• Remove electrical connection dust cap before

wiring.

• All threaded parts must be treated with water-

proofing sealant. (A non-hardening silicone
group sealant is recommended.)

• To prevent noise pickup, do not pass signal

and power cables through the same ducts.

• Explosion-protected instruments must be wired

in accordance with specific requirements (and,
in certain countries, legal regulations) in order
to preserve the effectiveness of their explosion-
protected features.

• The terminal box cover is locked by an Allen

head bolt (a shrouding bolt) on CENELEC,
SAA, and JIS flameproof type transmitters.
When the shrouding bolt is driven clockwise by
an Allen wrench, it is going in and cover lock is
released, and then the cover can be opened.
See Subsection 8.4 “Disassembly and Reas-
sembly” for details.

Refer to The Installation and Operating
Precautions for JIS Flameproof Equipment

and Installation and Operating Precautions
for JIS Intrinsically Safe Equipment
at the
end of this manual for correct wiring.

5.2 Selecting the Wiring Materi-

als

(a) Use stranded leadwires or cables which are the

same as or better than 600 V grade PVC insulated
wire (JIS C3307) or equivalent.

(b) Use shielded wires in areas that are susceptible to

electrical noise.

(c) In areas with higher or lower ambient temperatures,

use appropriate wires or cables.

CAUTION

If the transmitter is flameproof and the ambient
temperature is 50

°

C or more, use cables having

a maximum allowable heat resistance of at least
75

°

C in consideration of the instrument's genera-

tion of heat or the cables' self-heating.

(d) In environment where oils, solvents, corrosive gases

or liquids may be present, use wires or cables that
are resistant to such substances.

(e) It is recommended that crimp-on solderless terminal

lugs (for 4 mm screws) with insulating sleeves be
used for leadwire ends.

5.3 Connections of External

Wiring to Terminal Box

5.3.1 Power Supply Wiring Connection

Connect the power supply wiring to the SUPPLY +
and – terminals.

Power supply

+

Transmitter terminal box

F0501.EPS

Figure 5.3.1 Power Supply Wiring Connection

5.3.2 External Indicator Connection

Connect wiring for external indicators to the CHECK +
and – terminals.

(Note) Use a external indicator whose internal resistance is 10

or

less.

Transmitter terminal box

External indicator

F0502.EPS

Power supply

+

Figure 5.3.2 External Indicator Connection