6) integral indicator scale setup, User-set engineering unit display – Yokogawa EJA118 User Manual

Page 39

Advertising
background image

IM 1C22H1-01E

7-10

7. BRAIN TERMINAL BT200 OPERATION

(6) Integral Indicator Scale Setup

The following 5 displays are available for integral
indicators.

T0708.EPS

D20: DISP SELECT

and Display

NORMAL %

USER SET

USER & %

INP PRES

PRES & %

Indicates –5 to 110% range
depending on the Measurement
range (C21, C22).

Indicates values depending on the
Engineering range (D22, D23).

(

Note 1

)

Units set using Engineering unit
(D21) are not indicated.

Indicates user set and % alternately
in 3 second intervals.

Indicates input pressure. Indication
limits –19999 to 19999.

Indicates input pressure and %
alternately in 3 second intervals.

A10:OUTPUT (%)

45.6 %

Description

and Related parameters

A11:ENGR.OUTPUT

20.0 M

A10:OUTPUT (%)

45.6 %

A11:ENGR. OUTPUT

20.0 M

A40:INPUT

456 kPa

A10:OUTPUT (%)

45.6 %

A40:INPUT

456 kPa

(Note 1) Scale range can be specified with range limit specifications up

to 5 digits (excluding any decimal point) for low or high range

limits within the range of –19999 to 19999.

See (a.) through (c.) for each setting procedure.

% indication and
input pressure
indication

Transmitter is set

for “% display” when

shipped.

D20: DISP SELECT
NORMAL %
INP PRES
PRES & %

User-set engineering
unit display

D20: DISP SELECT
USER SET
USER & %

D21: DISP UNIT

D22: DISP LRV

D23: DISP HRV

Set for user-set
engineering unit display.

Set a unit to be
displayed on the BT200.

Set a numeric value for
engineering unit for 4 mA
output (LRV).

Set a numeric value for
engineering unit for 20 mA
output (HRV).

F0718.EPS

a. Display Selection (D20: DISP SELECT)

Follow the instructions given to the below to change
the range of integral indication scales.

When

USER SET

is selected, the user set values of

integral indication and

A11: ENGR. OUTPUT

parameter are indicated.

• Example: Set the integral indicator scale to

engineering units display.

The “%” disappears from the

integral indicator display.

ESC

SET
D20:DISP SELECT
USER SET

FEED

NO

OK

SET
D20:DISP SELECT
NORMAL %
<NORMAL %>
<USER SET>
<USER & %>
<INP PRES>

Use the or key

to select “USER SET.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0720.EPS

Advertising